for product data sheets, visit www .cooperb ussmann.com/pr oducts/da tasheet.asp 19 low voltage, branch circuit rated fuses low voltage branch circuit fuses lp-cc class cc specifications description: time-delay, current-limiting, rejection-type fuse C 12 seconds (minimum) at 200% rated amps. dimensions: 13 ? 32 x 1 1 ? 2 (10.3 x 38.1mm). construction: melamine tube. ratings: volts 600vac (or less) 300vdc ( 1 ? 2 -2 8 ? 10 a & 20-30a) 150vdc (3-15a) amps 1 ? 2 -30a ir 200,000a rms sym. 20,000a dc agency information: ce, std. 248-4, class cc, ul listed, guide jddz, file e4273, csa certified; class 1422-02, file 53787. features and benefits ? time delay coupled with class cc current-limiting response provides close sizing on small motor and relay circuits, and maximum component short-circuit current rating protection. ? 200,000a interrupting rating provides high ratings for control circuit locations. ? class cc rejection feature, with appropriate fuse block, prevents inserting lesser-rated supplementary fuses. ? inventory consolidation of 13 ? 32 x 1 1 ? 2 inch supplementary fuses reduces sku investment and minimizes potential for misapplying fuse. typical applications ? specialized circuits ? industrial control ? isolated, in-line fuse holder catalog numbers (amps) lp-cc- 1 2 lp-cc-2 1 2 lp-cc-7 1 2 lp-cc- 6 10 lp-cc-2 8 10 lp-cc-8 lp-cc- 8 10 lp-cc-3 lp-cc-9 lp-cc-1 lp-cc-3 8 10 lp-cc-10 lp-cc-1 1 8 lp-cc-3 1 2 lp-cc-12 lp-cc-1 1 4 lp-cc-4 lp-cc-15 lp-cc-1 4 10 lp-cc-4 1 2 lp-cc-20 lp-cc-1 1 2 lp-cc-5 lp-cc-25 lp-cc-1 6 10 lp-cc-5 6 10 lp-cc-30 lp-cc-1 8 10 lp-cc-6 lp-cc-2 lp-cc-6 1 4 lp-cc-2 1 4 lp-cc-7 low-peak time-delay, rejection-type fuses 200 100 10 time in seconds 1 .1 .01 ??? ???o ??o 1 1?? 3 3??? 4 4??? 6 8 10 12 15 20 25 30 ampere rating .4 1 10 100 1000 current in amperes time current characteristics?verage melt data sheet: 1023 (0-30) recommended fuse holders & blocks for class cc 600v fuses ? see page 8 10 20 30 40 50 60 80 100 200 300 400 500 600 800 1,000 2,000 4,000 3,000 2,000 1,000 800 600 400 300 200 100 80 60 40 30 20 10 50 500 30 25 ampere rating 20 15 2- 8 / 10 1- 1 / 4 prospective short-circuit currentCsymmetrical rms amps instantaneous peak let-through current in amps current limitation curves
|